The 10-Way Input Module (IM-10) provides ten individually addressable inputs for switch or relay contacts. The input status is reported to the fire panel via the analogue addressable (AA) loop.
Each input has a green LED indicator controlled by the fire panel.
Each input on the IM-10 has its own loop address. The first input's address may be configured to any value from 01 to 90, using rotary switches on the module. The other inputs are automatically assigned to the nine next higher addresses.
Up to two unused inputs may be disabled. This allows the unused addresses to be used for other equipment connected to the AA loop.
Click here for connection instructions.
Product Code
Description
IM-10
10 Way Input Module